Along an ordinary eave, outside air can reach a ventilation strip from the open side of the gutter. At a box gutter behind a parapet, the first course of clay tiles faces a wall. Copying the eave detail from the street elevation can put an inlet in a narrow pocket beside standing water.
The Clay Roof Tile Council’s box-gutter section identifies two questions for the designer. A high wall can restrict the approach of air to the inlet. A gutter that backs up because of debris or ice can allow water into the roof through the ventilator. A product’s stated opening area on its own answers neither question.
Show the inlet in the section through the gutter
Ask for the wall top, gutter lining, discharge and proposed inlet to be shown together. Have the designer trace the normal air path to the roof void and explain where water could rise if the outlet were obstructed. A detail drawn through the middle of the roof plane misses the wall and the inlet that need to be compared.
The Council illustrates the option of ventilation tiles clear of the wall and gutter if either condition makes the strip unsuitable. If that option is selected, show the tile positions and what space they ventilate. Separate the vent fittings from ordinary field tiles in the clay tile submittal. That gives the roofer a location to build to and the owner a place to identify during future maintenance.