A roof drawing can show enough room for the square base of a restaurant exhaust fan yet leave no room for someone to empty its grease collector. That matters when an adjoining slope gets new clay barrel tiles. The top of a cover tile or a raised flashing can occupy space that looks clear in plan.
Greenheck describes a trap on its CUE and CUBE upblast fans that collects grease discharged through the fan drain before it reaches the roof. The manufacturer calls for regular cleaning according to the amount collected. Its manual also illustrates hinged access for service. The mechanical equipment has two different space requirements: the path taken by the hinged fan and the space needed to reach and service the collector.
Review the arrangement with the person who cleans it
Ask the kitchen ventilation contractor for the installed fan model, hinge side, drain position and collector dimensions. On a section through the curb, draw the adjacent tiles at their finished height. On the plan, outline the open fan and indicate where maintenance staff can stand and reach the collector under the building’s access arrangements. If reaching the trap would require standing on unsupported tile, return the layout for revision.
Before accepting the work, have the responsible service contractor confirm that the collector is connected, reachable and serviceable and that the fan can be opened as intended. Give the owner a photograph identifying the collector and its service route. The roofer can then document the curb and flashing separately in the tile roof handover file.