During a slate reroof, replacing two aging exhaust caps with one can seem like a tidy way to reduce roof openings. The number of caps on the elevation tells the slater how many openings to flash. It tells the building owner little about where the air goes when only one bathroom fan runs.
Read the drawing from each bathroom toward the roof
Trace each fan to the point where the ducts join. At that junction, air pushed by the running fan can travel into the other bathroom through its idle fan. In the shared arrangement illustrated in ENERGY STAR’s HVAC installation guidebook, each fan has backdraft protection on its own branch. A damper at the roof cap alone leaves a path between the bathrooms below it.
Mark the two branches on the drawing. Beside each, enter the fan model and whether the mechanical contractor verified an integral damper or specified a separate one. A photo of the exterior cap answers neither question. If one fan serves a different purpose, identify that use before treating the pair as bathroom exhausts.
Set a decision point before the opening disappears
Have the mechanical designer check the proposed routing, duct sizes, fan performance and applicable requirements. Ask the contractor how delivery of air outdoors will be verified with either fan running and with both in operation. Give the slater a dated drawing identifying the opening to retain and the one to close once the arrangement is approved. Until then, carry the closure as a pending item in the roofing scope. This keeps a mechanical redesign from surfacing after the replacement slates are already in place.