The stairwell roof window opens. Has its smoke function been checked?

Separate everyday window operation from the smoke-control handover when renewing slate and flashing around a stairwell vent.

By the Slate, Tile & Metal Guild ·

At the end of a slate reroof, a site manager presses the stairwell window switch. The sash moves and the new apron looks dry. The switch confirms that the sash moves in normal use. The building manager still needs to know what happens when the smoke-control system calls for it to open. A powered window over a stair can also be part of the building’s smoke-control system.

VELUX gives a concrete example in its European product sheet for a GGL smoke ventilation window. In everyday ventilation mode the sash opens 200 mm. The stated fire position is approximately 90 degrees. A motor comes with the window, and the compatible smoke-control unit is supplied separately. The small opening someone sees at a wall switch therefore cannot establish that the smoke function has been reinstated.

Identify the window before pricing the roof work

Give the building manager a marked roof plan and ask which equipment record belongs to the unit. Have the responsible fire-safety professional confirm its function and arrange any temporary provisions needed during the works. The slate contractor can then price the surrounding slates and flashing against an identified assembly. If replacement is proposed, the designer needs the existing window and control references before agreeing to a substitution based on frame size.

On the closeout sheet, give the roofer a line for the completed slate and flashing detail. Give the smoke-control specialist a separate line for the commissioning record identifying the window, its control and the function verified. Ask the building manager who will receive that record and authorize return to service. The Guild’s guide to slate window flashing selections covers the weathering side of the same opening.

Further reading

VELUX — GGL smoke ventilation roof window, glazing 66SG, pp. 1 and 9. The cited guide describes a particular European window and control arrangement. Building-specific fire provisions and commissioning are for the responsible professionals.

Published by the Guild as part of Tim Kelly’s Slate Boss resource network. These educational guides support project conversations and do not replace an on-site inspection or a project specification.